Dwyer 616KD-04 Differential Pressure Transmitter
Models & Ordering
Filter By
2% acc, 4-20 mA
Model | Description |
616KD-04 | Differential pressure transmitter, 0 to 10″ w.c., 4-20 mA. |
MORE ABOUT THIS ITEM
These low-cost, compact transmitters reduce up-front costs as well as expenses over the life of the product. These transmitters are ideal for building automation applications such as air handlers, duct pressure, variable air volume, and filter monitoring. With the One-Touch digital push button, both zero and span are calibrated simultaneously. Just let the unit sit at zero reference pressure, then push the button. Mounting is simple with integral mounting holes on the molded housing; unit can also be mounted on a 35-mm DIN rail. A protective cap snaps directly on to the housing to cover wiring terminals.
Specifications & Description
Accuracy | ±2% full-scale |
Min Pressure (in WC) | 0 |
Max Pressure (in WC) | 2 |
Min Temperature (° F) | 32 |
Max Temperature (° F) | 122 |
Min Temperature (° C) | 0 |
Max Temperature (° C) | 50 |
Process Connection | 1/8″ and 3/16″ hose barbs |
Unit Of Measurement | ” WC |
Battery Type | 16 to 35 VDC |
Electrical Connections | Screw terminal |
Output | 4 to 20 mA |
Enclosure | RatingNEMA 1, IP20 |
Housing | Polycarbonate |
Media Compatibility | Air and noncombustible, compatible gases |
Description | Differential Pressure Transmitter, 4 to 20 mA Output, 10 IN WC |